Distributore LioN-Safety 16/8-F-DI M12 – Ethernet/IP / CIP Safety

    Richiesta informazioni

    Compila il form e invia una richiesta su questo prodotto





    Distributore LioN-Safety 16/8-F-DI M12 – Ethernet/IP / CIP Safety

     


    Download datasheet
    0980 SSL 3130-121-007D-202 ioN-Safety 16/8-F-DI M12 EtherNet/IP / CIP Safety , M12 L-coded Power Supply, Metal 60mm, IoT Protocols (OPC UA, MQTT, CoAP, REST)

    CONDIVIDI / SHARE

    Descrizione

    Product Description
    Brand: Belden
    Product Family: I/O Systems: Active – Standalone
    Product Sub Family: LioN-Safety
    Item Description: 0980 SSL 3130-121-007D-202
    Part Number: 935023005
    Device Type: FS I/O Device
    Protocol: CIP Safety
    I/O Function: 16/8 FS DI
    Bus Connection: M12 LAN, 4-poles, D-coded
    Power Connection (System Supply): M12 Power, 5-poles, L-coded
    I/O Connection: M12, 5-poles, A-coded
    I/O Type: Functional Safety Digital Input
    General Data
    Housing Material: Metal, Zinc Die-cast
    Housing Plating: Nickel, matt
    Housing Color: Grey Metallic
    Protection Degree / IP Rating**: IP65, IP67, IP69K
    Potted: Yes
    Dimensions (W x H x D): 60 mm x 31 mm x 200 mm
    Weight: approx. 500 g
    Ambient Temperature (Operation)*: -40 °C to 70 °C ( 2000m ASL 63°C)
    Ambient Temperature (Storage/Transport): -40 °C to 85 °C
    Permissible Humidity (Operation): 5 % … 98 % (For UL applications max. 80 %)
    Permissible Humidity (Storage/Transport): 5 % … 98 % (For UL applications max. 80 %)
    Air Pressure (Operation): 70 kPa … 106 kPa (up to 3000 m above sea level)
    Air Pressure (Storage/Transport): 70 kPa … 106 kPa (up to 3000 m above sea level)
    Flammabilty Class: UL 94 (IEC 61010)
    Protection Class: III, IEC 61140, EN 61140, VDE 0140-1
    Pollution Degree: 3 acc. to EN 60664-1, VDE 0110-1
    Vibration Resistance: 15 g / 5 -500 Hz
    Shock Resistance: 50 g / 11ms
    Mean Time To Failure (MTTF): 107 years. acc. to EN ISO 13849-1
    Contact Base Material: M12, D-coded, CuSn, Gold-plated | M12 Power, L-coded, CuNi, Gold-plated
    Contact Bearer Material: PA
    O-Ring Material: FKM
    Mounting: 2 hole screw mounting. Use standard M4 x 25 / 30 screws with toothed lock washer (as per DIN 125) and self-locking nuts.
    Fastening Torque (Fixing Screw): M4: 1 Nm
    Fastening Torque (Ground Connection (FE)): M4: 1 Nm
    Fastening Torque (Bus Connection): M12: 0.5 Nm
    Fastening Torque (Power Connection): M12: 0.5 Nm
    Fastening Torque (I/O Connection): M12: 0.5 Nm
    Included in Delivery: Attachable Labels: 15x, Sealing Caps: 5x M12
    Safety
    SIL/ SIL CL (IEC 62061/ IEC 61508): up to 3
    Performance Level IL (ISO 13849): up to e
    Category Cat. (ISO 13849): up to 4
    Probability of failure per hour (PFH): 1,32 E-9
    Mission Time: 20 years
    Safety Reaction Time: 42ms
    Safety Digital Inputs: 16/8
    Safety Digital Outputs: –
    EtherNet/IP
    Protocol (EtherNet/IP): EtherNet/IP
    Safety Communication: CIP Safety
    Connection: M12 LAN, 4-poles, D-coded
    Number of Connections: 2
    Specification: CIP V3.2x, EIP Adaption of CIP V1.2x
    Transmission Rate: Fast Ethernet (10/100 Mbit/s), Full Duplex
    Transmission Method: 100 BASE-TX, with auto negotiation and auto crossing
    Cycle Time / Requested Packet Interval (RPI): min. 1 ms
    Addressing: BootP, DHCP, Rotary Address Switches
    Address Switches Range: 0 to 255 dec
    Connection Types: Exclusive Owner, Input Only, Listen Only
    CIP Msg Connection Limit: 6
    CIP I/O Connection Limit: 3
    Device Level Ring (DLR): Supported, beacon based
    Quick Connect (QC): Supported, ≤ 500 ms
    Supported Network Protocols (Other): ACD, ARP, BootP, DHCP, HTTP, IGMP, Ping, TCP/IP
    IIoT Protocols
    OPC UA: Cyclic data read/write, Diagnosis data, Event data
    MQTT: Cyclic data read/write, Diagnosis data, Event data
    REST API: Cyclic data read/write, Diagnosis data, Event data
    CoAP: Cyclic data read/write, Diagnosis data, Event data
    Power Supply
    Connection Module Supply Voltage: M12 Power, 5-poles, L-coded
    Number of Connections: 2
    Current Carrying Capacity of Connector: max. 16 A
    Module Supply Voltage (Nominal): 24 V DC (SELV/PELV)
    Module Supply Voltage (Range): 18 V DC to 30 V DC
    Current Consumption (typ.): typ. 180mA (at 24 V DC)
    Reverse Polarity Protection: Yes
    Status Indicator (System Supply): LED green
    Diagnostic Indicator: LED red
    Connection Sensor Supply Voltage: M12 Power, 5-poles, L-coded
    Current Carrying Capacity of Connector: max. 16 A
    Sensor Supply Voltage (Nominal): 24 V DC (SELV/PELV)
    Sensor Supply Voltage (Range): 18 V DC to 30 V DC
    Reverse Polarity Protection: Yes
    Status Indicator (Sensor Supply): LED green
    Diagnostic Indicator: LED red
    Current Carrying Capacity of Connector: max. 16 A
    Actuator Supply Voltage (Nominal): 24 V DC (SELV/PELV)
    Actuator Supply Voltage (Range): 18 V DC to 30 V DC
    Reverse Polarity Protection: Yes
    Status Indicator (Actuator Supply): LED green
    Diagnostic Indicator: LED red
    Digital Input Channels
    Number of Digital Input Channels: up to 16
    Connection: M12, 5-poles, A-coded
    Number of Ports: 8x, X1 to X8
    Channel Type: Type 3 acc. to IEC 61131-2
    Input Wiring: 2-, 3-, 4-wire
    Nominal Voltage: 24 V DC via US (module power supply)
    Nominal Current: typ. 3 mA
    Sensor Current Supply: max. 1500 mA per port
    Sensor Type: PNP
    Input Voltage Range “0” signal: -3 V DC …+5 V DC
    Input Voltage Range “1” signal: 11 V DC … 30 V DC
    Input Filter Time: configurable
    Protective Circuit: Electronicaly: Overload protection, short-circuit protection
    Diagnostic Indicator: LED white or yellow per channel
    Digital Output Channels
    Status Indicator (Outputs): LED white or yellow per channel
    Diagnostic Idicator: LED red per channel
    Electrical Isolation
    US (System Supply Voltage) / FE: 32V DC (clamp voltage)
    US / UL (Actuator Supply Voltage): 500 V DC
    UL / FE: 32V DC (clamp voltage)
    Bus connection / FE: 2000 V DC
    EMC Conformance
    EMC Directive: 2014/30/EU
    EN 61000-4-2 Electrostatic Discharge (ESD): Criterion B; 4 kV contact discharge, 8 kV air discharge
    EN 61000-4-3 Electromagnetic Field: Criterion A; Field intensity: 10 V/m
    EN 61000-4-4 Fast Transients (Burst): Criterion B, 2 kV
    EN 61000-4-5 Surge Voltage: Criterion B; DC supply lines: ±0.5 kV/±0.5 kV (symmetrical/asymmetrical); For I/O ports with cables ≤ 30m
    EN 61000-4-6 Conducted immunity: Criterion A; Test voltage 10 V
    EN 55022 Radio Interference Properties: Class A
    EN 55032 Radio Interference Properties: Class A
    Safety & Environmental Compliance
    CE: Yes
    RoHS Compliant: Yes
    China RoHS-Compliant: Yes
    Approvals
    FS-Certification: TÜV (Rheinland) IEC 61508, ISO 13849
    UL: cULus Listed, UL 61010-1
    CSA: Yes, via UL
    ODVA: Yes
    IO-Link: Yes