T1Flo Vented Enclosure with Fan, Type 1

    Richiesta informazioni

    Compila il form e invia una richiesta su questo prodotto





    T1Flo Vented Enclosure with Fan, Type 1

    Applications: These enclosures have a thermostatically controlled forced-air ventilation system for the removal of heat. Ideal for control systems in HVAC or industrial environments that have a combination of heat-sensitive electronics with high heat producing components such as (VFD) drives, inverters, PLCs and non-hardened processors.
    Features:
    Active cooling ventilation system with factory installed, thermostatically controlled fan (115 VAC) and filter
    Terminal block power connection for fan
    Washable expanded metal filter
    Lift-off hinged door
    Slotted quarter-turn latch
    Collar studs for mounting optional panel
    Grounding provision on door and body
    Mounting holes on back of enclosure
    Accepts optional mounting foot kit
    Door gasket
    Specifications: 14 gauge steel
    Finish: ANSI 61 gray polyester powder paint finish inside and out over pretreated surfaces. Optional solid panels are white; optional perforated panels are gray.
    Accessories:
    Electric Heater
    Electrical Interlocks
    Grounding Device
    Locking T Handle
    Mounting Bracket Kits
    Panels for Type 3R, 4, 4X, 12 and 13 Enclosures
    Rack Mounting Angles – U Style (Type RA)
    Compact Cooling Fans
    Touch-Up Paint
    Steel and Stainless Steel Window Kits
    Notes:
    Required Airflow
    The following equation is used to calculate the airflow required in a forced-air system to remove heat and maintain enclosure temperature a given amount above the ambient temperature.
    CFM = WT x 3.16 / Tint – Tamb
    CFM = Required airflow (ft.3 / min.)
    WT = Total heat dissipated in enclosure (watts)
    Tamb = Ambient or external Temperature (degrees F)
    Tint = Desired internal Temperature (degrees F
    Assumptions: Specific values and physical sizes must be verified. Typical motor efficiency is 91 percent; typical drive efficiency is 97 percent.
    CONDIVIDI / SHARE

    Descrizione

    UL 508A Listed; Type 1; File No. E61997
    cUL Listed per CSA C22.2 No. 94; Type 1; File No. E61997
    NEMA/EEMAC Type 1
    IEC 60529, IP20

    Resta aggiornato

    Iscriviti alla News Letter per scoprire tutte le novità.

      Con l’iscrizione accetto l’informativa sulla privacy D.Lgs 196/2003